Mô đun GE FANUC IC693MDR390 24 Volts DC Input Relay Module Series 90-30
GE FANUC IC693MDR390 , 24 volts DC Input/Output Relay module , Series 90-30
Product Description
The IC693MDR390, manufactured by GE Fanuc, is a 24 volts DC Input/Output Relay module. This module provides 8 inputs and 1 common power input terminal and 8 normally-open relay circuits in the same module. The input circuits are compatible with either negative or positive characteristics in which they source or sink between input devices and the common user. These input circuits are arranged into one group for every 8 inputs. The circuits for relay output are arranged as two groups having four circuits for both. There is a common terminal for power output per group. Input characteristics are compatible with a huge range of devices. Proximity switches, push buttons, and limit switches are some of the devices compatible with the IC693MDR390 that may be useful for the user’s system. Field devices operate on user-supplied power.
The user provided output loads are controlled by relay circuits that are normally-open. Every output has two amps of switching capacity output. Relay outputs can control a wide variety of load devices supplied by the user, such as indicators, motors, and solenoids. The backplane has a +24 volts DC bus which provides the power for the relay circuits, which are internal. The field devices operate on AC source or DC source for power which must be supplied by the user. This module has no fuses. The module has indicators to provide the status of the device, indicating whether the device is ON or OFF. These indicators are LEDs which are ordered in rows and are green. There are labels for input points and output points and color-coding schemes on insert panels to avoid handling errors. This module is installable on every Input/output slot with either 5-slots baseplate or 10-slots baseplate.
Rated Voltage: | Inputs: 24 volts DC. Outputs: 24VDC or 120/240 VAC |
# of Outputs: | 16 (8 Inputs and 8 Outputs) |
Freq: | 50/60 Hz with AC |
Output Current: | 2 Amps per circuit, 4 amps per common |
Input Current: | 7.5 mA at rated voltage |
Output Voltage Range: | 5 to 30 volts DC, 5 to 250 volts AC |
Technical Information
Inputs | |
Rated Voltage | 24 volts DC |
Input Voltage range | –30 to +32 volts DC |
Inputs per Module | 8 (one group of eight inputs) |
Isolation | 1500 volts RMS between field and logic side |
500 volts RMS between inputs | |
Input Current | 7.5 mA (typical) at rated voltage |
Input Characteristics | |
On-State Voltage | 15 to 32 volts DC |
Off-State Voltage | 0 to +5 volts DC |
On-State Current | 4 mA (minimum) |
Off-State Current | 1.5mA (maximum) |
On Response Time | 7 ms typical |
Off Response Time | 7 ms typical |
Outputs | |
Rated Voltage | 24 VDC, 120/240 VAC |
Operating Voltage | 5 to 30 volts DC |
5 to 250 volts AC, 50/60 Hz | |
Outputs per Module | 8 (two groups of four outputs each) |
Isolation | 1500 volts RMS between field and logic side |
500 volts RMS between groups | |
Maximum Load 1 | 2 amps maximum per output |
4 amps maximum per common | |
Minimum Load | 10 mA |
Maximum Inrush | 5 amps |
On Response Time | 15 ms maximum |
Off Response Time | 15 ms maximum |
Internal Power Consumption | 80 mA (all I/O on) from +5V backplane bus |
70 mA (all outputs on) from relay +24V backplane bus |