Mô đun Redundant Power Supply Module GE Fanuc IC200MDL940 OUTPUT RELAY ISOLATED 2A FORM A 16PT
Redundant Power Supply Module GE Fanuc IC200MDL940 OUTPUT RELAY ISOLATED 2A FORM A 16PT
Module Characteristics
Points IC200MDL930: 8 individually isolated Form A relay outputs
IC200MDL940, BXIOOR162: 16 individually isolated Form A relay outputs
Module ID IC200MDL930: FFFF8040
IC200MDL940, BXIOOR162: 80408040
Isolation:
User input to logic (optical) and frame ground: 250VAC continuous; 1500VAC for 1 minute
IC200MDL930: Group to Group: not applicable
IC200MDL940, BXIOOR162: Group to group: 250VAC continuous; 1500VAC for 1 minute
Point to point:: 250VAC continuous; 1500VAC for 1minute
LED indicators One green LED per point shows individual point on/offstate
OK LED indicates backplane power is present Backplane currentconsumption
IC200MDL930: see graph
IC200MDL940, BXIOOR162, 5V output:: 490mA maximum
External power supply 0 to 125VDC, 5/24/125VDC nominal
0 to 265VAC (47 to 63Hz), 120/240VAC nominal
Thermal derating None
Output Characteristics
Output voltage 0 to 125VDC, 5/24/125VDC nominal
0 to 265VAC (47 to 63Hz), 120/240VAC nominal
Output voltage drop 0.3V maximum
Load current 10mA per point minimum
2.0A for 5 to 265VAC maximum (resistive)
2.0A for 5 to 30 VDC maximum (resistive)
0.2A for 31 to 125 VDC maximum (resistive)
Output leakagecurrent Not applicable (open contact)
On response time 10ms maximum
Off response time 10ms maximum
Protection No internal fuses or snubbers
Switching frequency 20 cycles per minute (inductive load)
Relay type Fixed coil, moving armature
Contact type Silver alloy
OTHER SUPERIOR PRODUCTS
Yasakawa Motor, Driver SG- | Mitsubishi Motor HC-,HA- |
Westinghouse Modules 1C-,5X- | Emerson VE-,KJ- |
Honeywell TC-,TK- | GE Modules IC – |
Fanuc motor A0- | Yokogawa transmitter EJA- |
Relay Output Modules IC200MDL940 (shown below) and BXIOOR162 provide 16 individually-isolated Form A relay outputs.
The contact is closed when the host CPU is active and the corresponding output logic bit is “1”.
Intelligent processing for this module is performed by the CPU or NIU.
The green OK LED is ON when backplane power is present to the module.
unpacking the equipment, record all serial numbers. Save the shipping containers and packing material in case it is necessary to transport or ship any part of the system.
C, D OR NON-HAZARDOUS LOCATIONS ONLY
• WARNING – EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2;
• WARNING – EXPLOSION HAZARD – WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE REPLACING OR WIRING MODULES; AND
• WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS.
When wiring outputs to inductive loads, use of external suppression circuits is recommended. See chapter 2, “Installing Wiring for I/O
Devices-Wiring to Inductive Loads” in the VersaMax I/O System Manual, GFK-1504, for more information.
If hot insertion of a module is done improperly, the operation of other modules on the same backplane may be disrupted. See Installing a
Module on a Carrier in the VersaMax Modules Manual, GFK-1504.