Mô đun PM865K01 3BSE031151R1 Digital I O Module 24 V DC (19.2-30 V DC) 287 / 487 mA
đại lý PM865K01 3BSE031151R1 | nhà phân phối PM865K01 3BSE031151R1
PM865K01 3BSE031151R1 Digital I O Module 24 V DC (19.2-30 V DC) 287 / 487 mA
The CPU board contains the microprocessor and RAM memory, a real-time clock, LED indicators, INIT push button, and a CompactFlash interface.
The base plate of the PM865 controller has two RJ45 Ethernet ports (CN1, CN2) for connection to the Control Network, and two RJ45 serial ports (COM3, COM4). One of the serial ports (COM3) is an RS-232C port with modem control signals, whereas the other port (COM4) is isolated and used for the connection of a configuration tool. The controller supports CPU redundancy for higher availability (CPU, CEX-Bus, communication interfaces and S800 I/O).
The high integrity functionality is enabled by the addition of a SM81x module and the SIL certified software. This enables non-critical control schemes to be upgraded to SIL certified schemes by the addition of a plug-in SM81x module, plus selection of the appropriate software. The AC 800M High-Integrity also offers IEC 61508 and TÜV-certified control environment for combining safety and business critical process control in one controller unit without sacrificing the safety integrity.
Features and benefits
- AC 800M High SIL 2 certified using PM865/SM810/SM811 or PM867/SM812
- AC 800M High SIL 3 certified using PM865/SM811 or PM867/SM812
- Supports S800 I/O High Integrity (PM865, PM866A and PM891)
- The controller can be configured with 800xA control builder
- The controller has full EMC certification
- TÜV Certified SIL 2 and SIL 3
- Built-in redundant Ethernet Communication ports
Article number | 3BSE031151R1 (PM865K01) |
Redundancy | No |
High Integrity | Yes |
Clock Frequency | 96 MHz |
Performance, 1000 boolean operations | 0.17 ms |
Performance | 0.17 ms |
Memory | 32 MB |
RAM available for application | 22.184 MB |
Flash memory for storage | No |
Processor type | MPC862P |
Switch over time in red. conf. | Max 10 ms |
No. of applications per controller | 32 |
No. of programs per application | 64 |
No. of diagrams per application | 128 |
No. of tasks per controller | 32 |
Number of different cycle times | 32 |
Cycle time per application programs | Down to 1 ms |
Flash PROM for firmware storage | 4 MB |
Power supply | 24 V DC (19.2-30 V DC) |
Power consumption +24 V typ/max | 287 / 487 mA |
Power dissipation typ. | 6.9 W (11.4 W max) |
Redundant power supply status input | Yes |
Built-in back-up battery | Lithium, 3.6 V |
Real-time clock stability | 100 ppm (approx. 1 h/year) |
Clock synchronization | 1 ms between AC 800M controllers by CNCP protocol |
Event queue in controller per OPC client | Up to 3000 events |
AC 800M transm. speed to OPC server | 36-86 events/sec ,113-143 data messages/sec |
Comm. modules on CEX bus | 12 |
Supply current on CEX bus | Max 2.4 A |
I/O clusters on Modulebus with non-red. CPU | 1 electrical, 7 optical |
I/O clusters on Modulebus with red. CPU | 0 eletrical + 7 optical |
I/O capacity on Modulebus | Max 96 (single PM865) or 84 (red. PM865) I/O modules |
Modulebus scan rate | 0 – 100 ms (actual time depending on number of I/O modules) |
Supply current on Electrical Modulebus | 24 V : max 1.0 A 5 V : max 1.5 A |
Ethernet channels | 2 |
Ethernet interface | Ethernet (IEEE 802.3), 10 Mbit/s, RJ-45, female (8-pole) |
Control Network protocol | MMS (Manufacturing Message Service) and IAC (Inter Application Communication) |
Recommended Control Network backbone | MMS (Manufacturing Message Service) and IAC (Inter Application Communication) |
RS-232C interface | 2 (one general, 1 for service tool) |
RS-232C interface (COM3) (non red. only) | RS-232C, 75-19 200 baud, RJ-45 female (8-pole), not opto isolated, full RTS-CTS support |
RS-232C interface (COM4) (non red. only) | RS-232C, 9 600 baud, RJ-45 female (8-pole), opto isolated, no RTS-CTS support |
Temperature, Operating | +5 to +55 °C (+41 to +131 °F) |
Temperature, Storage | -40 to +70 °C (-40 to +158 °F) |
Temperature changes | 3 °C/minutes according to IEC/EN 61131-2 |
Altitude | 2000 m according to IEC/EN 61131-2 |
Pollution degree | Degree 2 according to IEC/EN 61131-2 |
Corrosion protection | G3 compliant to ISA 71.04 |
Relative humidity | 5 to 95 %, non-condensing |
Emitted noise | < 55 dB (A) |
Vibration | 10 < f < 50 Hz: 0.0375 mm amplitude, 50 < f < 150 Hz: 0.5 g acceleration, 5 < f < 500 Hz: 0.2 g acceleration |
Rated Isolation Voltage | 500 V a.c. |
Dielectric test voltage | 50 V |
Protection class | IP20 according to EN 60529, IEC 529 |
Emission & Immunity | EN 61000-6-4, EN 61000-6-2 |
Environmental conditions | Industrial |
CE- marking | Yes |
Electrical Safety | EN 50178, IEC 61131-2, UL 508 |
Hazardous location | cULus Class 1, Zone 2, AEx nA IIC T4, ExnA IIC T4Gc X |
Marine certificates | ABS, BV, DNV-GL, LR, RS, CCS |
TUV Approval | Yes |
RoHS compliance | – |
WEEE compliance | DIRECTIVE/2012/19/EU |
【Honeywell】Module DCS/PLC&Pressure Transmitter
【Yamatake】Switch&Pressure Transmitter
【AB】(AB/Rockwell) 17 Series & 2711 Series PLC
【ABB】Module DCS&PLC
【Yokogawa】Pressure Transmitter
【Reliance】Module DCS&PLC
【GE/Fanuc】IC69 Series,PLC
【Modicon】Module DCS&PLC
【Emerson/Delta V】Module DCS&PLC
(Fisher,Rosemount,Siemens,Mitsubishi,Yaskawa,SICK,NORGREN,Phoenix,Foxboro,Omron,Oilgear….)
Contact:
Similer item we can supply:
CI801 3BSE022366R1
CI810B 3BSE020520R1
CI820V1 3BSE025255R1
CI840A 3BSE041882R1
TK212A 3BSC630197R1
TU846 3BSE022460R1
TU847 3BSE022462R1
CI867K01 3BSE043660R1
3BSC950107R3
PM866K02 3BSE050199R1
AI801 3BSE020512R1
AO801 3BSE020514R1
DI801 3BSE020508R1
DI802 3BSE022360R1
DI803 3BSE022362R1
DO801 3BSE020510R1
DO802 3BSE022364R1
AI810 3BSE008516R1
AI815 3BSE052604R1
AI820 3BSE008544R1
AI825 3BSE036456R1
AI830A 3BSE040662R1
AI835 3BSE008520R1
AI835A 3BSE051306R1
AI843 3BSE028925R1
AI845 3BSE023675R1
AI890 3BSC690071R1
AI893 3BSC690141R1
AI895 3BSC690086R1
AO810V2 3BSE038415R1
AO815 3BSE052605R1
AO820 3BSE008546R1
AO845A 3BSE045584R1
AO890 3BSC690072R1
AO895 3BSC690087R1
DI810 3BSE008508R1
DI811 3BSE008552R1