Mô đun Ge Fanuc IC660BBR100 , Normally Closed Relay Output Block , 115 VAC or 230 VAC
Technical Information
Specifications
Block Type: CatalogNumbers: Output Block, Normally–Closed Relays TerminalAssemblyonly ElectronicsAssemblyonly Output Block, Normally-Open Relays TerminalAssemblyonly ElectronicsAssemblyonly |
16 circuit relay outputs in four isolated groups of four
IC660BBR100 IC660TBR100 IC660EBR100 IC660BBR101 IC660TBR101 IC660EBR101 |
Size (height x width x depth): Weight LEDs (I/O Block) LEDs (each circuit) |
8.83” (22.44cm) x 3.50” (8.89cm) x 3.94” (10.00cm) 4 lbs. (1.8 kg) UnitOK,I / OEnabled Individual relay coilstate |
EnvironmentalSpecifications: Operatingtemperature Storagetemperature Humidity Vibration |
0C to +60C (32F to +140F) –40C to +100C (–40F to +212F) 5 to 95% (non–condensing) 5–10Hz 0.2” (5.08mm) displacement; 10–200Hz at 1G |
Block PowerSupply: Frequency Operatingvoltage Power requirement Power supplydropouttime Isolation: Alloutputs to chassis ground Between output groups Power terminals to chassis ground Power terminals to outputs Comms terminals to power terminals Comms terminals to outputs HeatDissipation |
47–63 Hz (115VAC) 93VAC to 132VAC; (230VAC) 185VAC to 265VAC 87mA at 115 VAC 1 cycle 1500 VAC 1500 VAC 1700 VDC 1500 VAC 1700 VDC 1500 VAC 10.1 watts maximum with 16 outputs on |
OutputCharacteristics: Maximum Output current Maximumswitchingpower Maximuminrush current Output OFF leakage current Maximumswitchingfrequency Output turn–on delay (maximum) Output voltage range Minimumrecommendedload |
2 amps per circuit 60 Watts or 125 VA 2 amps per circuit 0.1mA 20cycles / minute(inductiveloads) 5mS 5V to 250V AC or 5V to 220V DC 10mA |
Relay Type Initial Contact Resistance |
Fixed coil moving armature 100 milliohms, maximum |
Typical Life: OperatingVoltage: 250VAC 250VAC 125VAC 220VDC 110VDC 30VDC 30VDC 12VDC |
MaximumCurrentforLoadType*TypicalLife ResistiveLampSolenoid(operations) 0.5A––––200,000 ––0.1A0.1A100,000 1.0A0.2A0.3A100,000 0.3A––––100,000 0.6A––––100,000 2.0A––––500,000 ––0.2A0.3A100,000 ––0.3A0.5A100,000 |
Effect of AdditionalCurrent onOperatingLife: 250VAC 125VAC 30VDC 12VDC |
Current inLoadTypeTypicalLife ResistiveLampSolenoid(operations) 0.1A––––1,500,000 0.3A––––1,000,000 1.0A––––2,000,000 2.0A––––1,000,000 *LamploadsaredefinedasaX10inrushwithapowerfactor(PF)of 1.00;whenturnedOFF,theyrepresentaPFof1.00.Solenoidsarede- finedasaX10inrushwithaPFof0.65;whenturnedOFF,theyrepre- sent a PF of 0.35. |
Ge Fanuc IC660BBR100 , Normally Closed Relay Output Block , 115 VAC Or 230 VAC
Product Description
The IC660BBR100 is a Normally Closed Relay Output Block. This block provides 16 output circuits in four independent groups with four relay-type outputs each.
Relay Blocks in the Genius I/O product family arrange outputs in groups of four, and each output can be powered by its own AC or DC source. Because IC660BBR100 is normally closed rather than normally open, it remains in a conductive state when de-energized. Block power for IC660BBR100 can be factory set at 115 VAC or 230 VAC (optional). Voltage selection is made by jumpers on the block’s terminal assembly.
Isolation between output circuit groups is 1500 VAC. This block can be used with a wide range of low-power control and indicating devices, including lamps, contactors, and relays. The Relay Output Block behavior can be customized for the environment by way of a handheld monitor. The user can set defaults for output power-up actions, establish whether output reverts to previous state or factory settings during electrical communication interruption, and select a CPU redundancy type. IC660BBR100 can also be designated for bus switching module control.
IC660BBR100 is versatile enough to handle a useful voltage range of 5 to 250 VAC or 5 to 220 VDC. LEDs in the block’s chassis signal unit and I/O conditions. A blinking LED indicates circuit faults. OFF (dark) suggests a defective block; however, the block may simply be lacking appropriate power supply. The ON status confirms expected performance.
Rated Voltage: | 115 VAC or 230 VAC |
# of Points: | 16 |
Input Range: | N/A |
Load Current: | 2 Amp |
Operating Voltage: | 93-132 VAC / 185-265 VAC |
Points per Common: | Four groups of 4 |