Mô đun Ge Fanuc IC660BBD101 , Low Leakage Input/Output Block , 115 Volt AC
Ge Fanuc IC660BBD101 , Low Leakage Input/Output Block , 115 Volt AC
Product Description
IC660BBD101 is a GE Fanuc Low Leakage Input/Output Block that comes with eight discrete points/circuits and delivers 115 Volts AC. The input, as well the as operating voltage range, is between 93-132 Volts AC with a load current of 2 Amps. Each of its eight circuits can be configured for either input or output. The I/O block links multiple discrete sensors/actuators and a communication bus. The block can accommodate high input impedance. A fuse shuts down output current in the circuit if it goes beyond 30 Amps or 20 Amps for every two cycles. The circuit can later be restored by issuing a command from the CPU or a handheld monitor.
The I/O block comes with features such as input filters with selectable filter times ranging from 10ms -100ms, module control for bus switching, output feedback for voltage monitoring, pulse testing for output points, and defaults for output power-up. The IC660BBD101 block comes equipped with salient diagnostics such as voltage overload detection, power-off, and no-load detection.
LED indicators on the I/O block blink to alert the user to errors or faults such as faulty cabling, incorrect baud rate, and improper grounding among others. There is a dedicated LED for each circuit. For an output circuit, an LED, which in ON indicates that a specific circuit has complied with the command issued by the CPU. For an input circuit, however, an ON LED shows that a specific terminal has reached the threshold voltage. Error messages are generated on the handheld monitor, which helps the user attend to the fault promptly and efficiently.
The IC660BBD101 I/O block weighs 4lbs and works with model IC660HHM501 of the handheld monitor and IC693BEM331 bus controller model. During block mounting, the I/O block should be installed in a protective enclosure, which is clean and devoid of any contaminants. Furthermore, there should be adequate cooling space for the block. Mounting can be done right-side up or upside down.
Rated Voltage: | 115 volt AC |
# of Points: | 8 |
Input Range: | 93-132 VAC |
Load Current: | 2 Amps |
Operating Voltage: | 93-132 VAC |
Points per Common: | One group of 8 |
Technical Information
Specifications
Blocktype: CatalogNumbers: Block: TerminalAssemblyonly: ElectronicsAssemblyonly: |
8 circuit combination input and output
IC660BBD101 IC660TSD100 IC660EBD101 |
Size (height x width x depth): Weight: LED’s (I/O block): LED’s (each circuit): Block to Block Isolation: HeatDissipation: |
8.83” (22.44cm) x 3.50” (8.89cm) x 3.94” (10.00cm) 4 lbs. (1.8 kg) UnitOK,I / OEnabled On logic side of switch 1500 V 16W maximum with 8 inputs 43.5W maximum with 8 outputs on at 2 amps. |
Standbypower(allinputsandoutputsoff): Operatingvoltage(singlesource): Frequency: Power supplydropouttime: |
8.5 Watts 93–132 VAC 47–63 Hz 1 cycle (16.7mS at 60Hz, 20mS at 50Hz) |
InputCharacteristics: Non–tristate input, OFF state: Minimum voltage across input device (IN to H) Maximum leakage through input device Non–tristate input, ON state: Maximumvoltageacrossinputdevice(INtoH) Maximumswitchcurrentthreshold Tristate input, OFF state: Acceptable voltage across input device (IN to H) Tristate input, ON state: Maximumvoltageacrossinputdevice(INtoH) Input loadnetwork: Resistor to N Capacitor to H Input processing time (typical) Selectable input filter times Inputdiagnostics |
60 VRMS |
1.5 mA | |
20 VRMS | |
6 mA RMS | |
16 VRMS–40 VRMS | |
4 VRMS | |
13K ohms | |
.10 ïf | |
2mS + filter | |
10 to 100mS in 10mS increments | |
Open Wire, Overtemperature, Failed Switch | |
OutputCharacteristics: Circuit output current (steady state) Maximum inrush current up to 2 cycles Maximum inrush current 2–6 cycles Maximum block output current Output Leakage @ 115 VAC: Current at 0 volt output (OUT to N) Voltage at open output (OUT to N) Outputswitch(OFFtoON/ONtoOFF) Maximumswitching frequency Turn–on delay (maximum) Voltage drop (at 2 amps) Voltage drop (at 30 amps inrush) Recommended min. load, resistive (No Load disabled): Recommended min. load, inductive (No Load dis- abled): No Load enabled threshold Fusing Outputdiagnostics |
2 amps RMS |
25 amps peak | |
14 amps peak | |
15 amps at 35C, 7.5 amps at 60C | |
< 7mA | |
65 volts | |
Zerocrossing | |
Once per second (high inrush currents) | |
0.5 Hz + 1mS | |
2.5 volts | |
10 volts | |
25mA | |
40mA | |
50mA | |
Internal electronic short circuit trip. 100ms long time trip | |
Short Circuit, Overload, No Load, Failed Switch, Overtemperature | |
Environmental: Operating Temperature Storage Temperature Humidity Vibration |
0 to +60 C (32 to +140 F) |
–40 to +100 C (–40 to +212 F) | |
5% to 95% (non–condensing) | |
5–10 Hz 0.2” (5.08mm) displacement, 10–200 Hz at 1G |