Mô đun ABB DO828 3BSE069055R1 16 channel relay digital output module for the S800 I/O
ABB DO828 3BSE069055R1 16 channel relay digital output module for the S800 I/O
Description of DO828
The DO828 is an 16 channel 125V d.c. / 250V a.c. relay output module for the S800 I/O. The maximum output voltage is 125V d.c. / 250V a.c. and the maximum continuous output current is 2A. All outputs are individually isolated.
Each output channel consists of optical isolation barrier, output state indication LED, relay driver, relay and EMC protection components.
The relay supply voltage supervision, derived from the 12 V distributed on the ModuleBus, gives an error signal if the voltage disappears, and the Warning LED turns on. The error signal can be read through the ModuleBus. This supervision can be enabled/disabled with a parameter.
General Information
Type | Digital Output |
Signal specification | 125 V d.c. / 250 V a.c., (5 – 125 V d.c. / 5 – 250 V a.c.), 2 A |
Article number | 3BSE069055R1 |
Number of channels | 16 |
Signal type | Relay (NO) |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Detailed data
Isolation | Individually isolated, channel-to-channel and to circuit common |
Maximum field cable length | 600 meters (656 yards) |
Rated insulation voltage | 250 V |
Dielectric test voltage | 2000 V a.c. |
Power dissipation | Typ. 3.5 W |
Current consumption +5 V Modulebus | 45 mA |
Current consumption +24 V Modulebus | 80 mA |
Current consumption +24 V external | 0 |
Diagnostics
Front LED’s | F(ault), R(un), O(SP) Channel 1-16 Status |
Supervision | 12 V Relay power converter monitor |
Status indication of supervision | Module Error, Module Warning, Channel Error |
I/O Modules
AI801 | AI810 | AI815 | AI820 | AI825 |
AI830A | AI835A | AI843 | AI845 | AI880A |
AI890 | AI893 | AI895 | AO801 | AO810V2 |
AO815 | AO820 | AO845A | AO890 | AO895 |
DI801 | DI802 | DI803 | DI810 | DI811 |
DI814 | DI818 | DI820 | DI821 | DI825 |
DI828 | DI830 | DI831 | DI840 | DI880 |
DI890 | DO801 | DO802 | DO810 | DO814 |
DO815 | DO818 | DO820 | DO821 | DO828 |
DO840 | DO880 | DO890 | DP820 | DP840 |
Features and benefits
- 16 channels for 125V d.c. / 250V a.c. relay outputs
- 16 isolated channels
- Output status indicators
- OSP sets outputs to predetermined state uponerror detection
Compability
Use with MTU | TU851 |
Keying code | ED |
Dimensions
Height | 119 mm (4.7″) |
Width | 45 mm (1.77″) |
Depth | 102 mm (4.01″), 111 mm (4.37″) including connector |
Weight | 0.18 kg (0.4 lbs.) |
Some ABB items sold by WTL:
WTL is not liable for any personal injury or property damage resulting from the use of this equipment. It is
buyer’s responsibility as to the safe handling & operation of this equipment and to verify equipment is
compliance to their machinery.
Our Brands:
【Honeywell】 | Module DCS/PLC/Transmitter |
【Emerson/Delta V】 | Module/ CT Motor & Drives |
【ABB】 | I/O Module |
【AB】 | Module&Touch Screen |
【Rosemount】 | Transmitter |
【Yokogawa】 | Transmitter |
【Yaskawa】 | Servo Drive&Servo Motor |
【GE/Fanuc】 | IC69 Series PLC |
【Mitsubishi】 | Servo Drive&Servo Motor |
(Modicon,SMC,SICK,NORGREN,Siemens,Ebmpapst etc.)