Bộ lập trình Full Duplex Exchange PLC Programmable Logic Controller SCHNEIDER 140NOC78100
PLC Programmable Logic Controller SCHNEIDER 140NOC78100 COMMUNICATING MOUDLE
SIL
NOTE: For complete definitions and parameters related to SIL ratings refer tomIEC 61508, “Functional safety of electrical/electronic/programmable electronic safety related systems”. Provided here is a partial definition. safety integrity level discrete level (1 out of a possible 4) for specifying the safety integrity requirements of the safety functions to be allocated to the E/E/PE safety-related systems, where safety integrity level 4 has the highest level of safety integrity and safety integrity level 1 has the lowest
(Definition IEC 61508) SIL2 project (application)
A project (application) that uses a Quantum Safety PLC (140 CPU 651 60S V1.00 or 140 CPU 671 60S V1.00) to implement Safety Functions in a Safety-Related System.
SIL3 project (application)
A project (application) that uses a Quantum Safety PLC (140 CPU 651 60S V2.00 or 140 CPU 671 60S V2.00) to implement Safety Functions in a Safety-Related
System.
SIR
Safety Integrity requirement
Safety Integrity requirements are derived from a risk assessment and describe the likelihood of a Safety Function to be performed satisfactorily, for instance the degree of certainty necessary for the Safety Function to be carried out.
sniffing reading the configuration out of a PLC
SRS
safety requirements specification
specification containing all the requirements of the safety functions that have to be performed by the safety-related systems
(Definition IEC 61508
Specifications
Manufacturer: | Modicon Quantum |
Series: | Communications |
Weight: | Ask |
Product or component type: | Ethernet control module |
Product compatibility: | 140CPU6xxxx |
Communication port protocol: | Modbus TCP |
Ethernet/IP | |
Exchange mode: | Full duplex |
Maximum number of connections: | 64 |
Transmission rate: | 10/100 Mbit/s |
Redundancy: | Yes hot standby redundant architecture |
Topology: | Daisy chain loop |
Redundant ring | |
Web server: | Embedded |
Communication service: | Embedded router |
CIP implicit messaging (I/O communication) | |
NTP time synchronization | |
FDR server | |
DHCP/BootP server | |
SMTP e-mail notification | |
Device Type Manager (DTM) | |
SNMP agent | |
Quality of Service (QoS) | |
CIP Explicit messaging (client messaging) | |
Embedded 4-port switch | |
Ethernet service: | Rapid Scanning Tree Protocol (RSTP) |
Transmission support medium: | Twisted pair |
Port Ethernet: | 10BASE-T/100BASE-TX, connector type: RJ45 |
Marking: | CE |
Supply: | Via the power supply of the rack |
Local signalling: | 1 LED green for communication on the bus (Active) |
1 LED green for configuration status (Ready) | |
1 LED green/red for device network status (Net Status 1) | |
1 LED green/red for extended DIO network status (Net Status 2) | |
1 LED green/red for module status (Mod Status) | |
1 LED green/red for network communication status (Net Status) | |
Module format: | Standard |
OTHER SUPERIOR PRODUCTS
Yasakawa Motor, Driver SG- | Mitsubishi Motor HC-,HA- |
Westinghouse Modules 1C-,5X- | Emerson VE-,KJ- |
Honeywell TC-,TK- | GE Modules IC – |
Fanuc motor A0- | Yokogawa transmitter EJA- |
Similar Products
140DDI35300
140DDI84100
140DDI85300
140DAI74000
140DAI75300
140DAO85300
140DAO84000
140DAO84210
140DDO35300
140DDO84300
140DRA84000
140EHC10500
140EHC20200
140ERT85410
140NOM21100
140XTS00200
140XBE10000
140XCA71703
140XCA71706
140XCP51000
The code of the last fault detected is given in this word. The following error codes cause the PLC to
stop if %S78 is set to 1. %S15, %S18 and %S20 are activated independently of %S78:
16#0002: PCMCIA signature not verified
16#2258: execution of HALT instruction
16#2302: call to a not supported system function in a user function block
16#9690: error of application CRC detected in background
16#DE87: calculation error on floating-point numbers (%S18, these errors are listed in the
word %SW17)
16#DEB0: watchdog overflow (%S11)
16#DEF1: character string transfer error (%S15)
16#DEF2: arithmetic or division by 0 error (%S18)
16#DEF3: index overflow (%S20)
Note: The codes 16#8xxx and 16#7xxx do not mstop the application and indicate an error on
function blocks. In case of a SIL3 related error, the PLC stops. After power off and restart of the PLC, %SW 125 contains the code of the cause of the error:
0x5AF1: sequence check error (unpredictableexecution in CPU)
0x5AF2: error in memory (corrupt address)
0x5AF3: comparison error (execution results of Intel and application processor differ)
0x5AF4: real-time clock error
0x5AF5: error initializing double codeexecution
0x5AF6: watchdog activation error
0x5AF7: error during memory check (takes more than 8 hours)
0x5AF8: error in memory check (corrupt RAM)
Note: %SW125 is only reset after init orcomplete download or restart (it always contains the last fault detected).