Bộ lập trình 125V 40W PLC Programmable Logic Controller IC695PSA040F GE Fanuc Power Supply
PLC Programmable Logic Controller GE Fanuc IC695PSA040F RX3i PacSystem IC695PSA040power supply
Product Description
The IC695PSA040 is a 120/240 volt AC or 125 volt DC, 40 Watt Power Supply from the GE Fanuc RX3i Series. See specifications for this unit on IC695PSA040’s website page.
Output Power: 40 Watts max
Output Voltage: 24 VDC, 5.1 VDC or 3.3 VDC
Output Current: 0-1.6 A, 0-6 A, or 0-9 Amps
Rated Voltage: 120/240 VAC or 125 VDC
Input Voltage Range: 85 to 264 VAC or 100 to 300 VDC
Number of Slots: 2
Specifications
Nominal Rated Voltage Input Voltage Range AC DC |
120/240 VAC or 125 VDC
85 to 264 VAC 100 to 300 VDC |
Input Power (Maximum with Full Load) |
70 Watts maximum |
Inrush Current | 4 Amps, 250 milliseconds maximum * |
Output Power |
40 Watts maximum total 5.1 VDC = 30 Watts maximum 3.3 VDC = 30 Watts maximum The maximum total output power available depends on the surrounding air temperature, as shown. |
Output Voltage |
24 VDC: 19.2 VDC to 28.8 VDC 5.1 VDC: 5.0 VDC to 5.2 VDC (5.1 VDC nominal) 3.3 VDC: 3.1 VDC to 3.5 VDC (3.3 VDC nominal) |
Output Current |
24 VDC: 0 to 1.6 Amps 5.1 VDC: 0 to 6 Amps 3.3 VDC: 0 to 9 Amps |
Isolation (input to backplane): | 250 VAC continuous; 1500 VAC for 1 minute |
Ripple (all outputs) | 150 mV |
Noise (all outputs) | 150 mV |
Ride-through time | 20 ms. This is the length of time the Power Supply maintains valid outputs if the power source is interrupted |
Wiring Terminals | Each terminal accepts one 14 AWG to 22 AWG wire. |
Current per Terminal | 6 Amps |
Number of Daisy-Chained PSA040 Supplies | Up to 4 |
Revision History
Version | Date | Details |
IC695PSA040J | May 2013 | Increases the margin of the 5V and 3.3V under voltage detectors to prevent PS faults during power-up. |
IC695PSA040H | Aug. 2012 | Resolves an issue with powering up under light loads. |
IC695PSA040G | Jun. 2011 | Hardware modification improves radiated RF susceptibility and removes the requirement to install control systems that use this product in a grounded metal enclosure to meet the EU EMC Directive. |
IC695PSA040F | Sep. 2006 | Hardware modification. Previous versions of this Power Supply occasionally failed to power up when installed in a 16-Slot Universal Backplane, IC695CHS016. This update resolves the issue. |
IC695PSA040E | Mar. 2006 |
The D version of this Power Supply (IC695PSA040D) incorrectly reported that it was a PSA140 power supply, causing a Configuration Mismatch error. The E version and versions prior to D report their identification correctly. |
IC695PSA040A | Oct. 2005 | Initial release |
- +5.1 VDC output
- +24 VDC relay output that can be used to power circuits on Output Relay modules
- +3.3 VDC which, is used internally by RX3i modules with IC695 catalog numbers
How many IC695PSA040’s can be installed in a PACSystems RX3i Universal Backplane?
Only 1
With what can IC695PSA040 not be used?
This power supply cannot be used with other RX3i power supplies in redundant or increased capacity modes.
What do the 4 LEDs indicate?
Power (Green/Amber). When this LED is green, it indicates power is being supplied to the backplane. When this LED is amber, power is applied to the power supply, but the power supply switch is off.
P/S Fault (Red). When this LED is lit, it indicates the power supply has failed and is no longer supplying sufficient voltage to the backplane.
Over Temperature (Amber). When this LED is lit, it indicates the power supply is near or exceeding its maximum operating temperature.
Overload (Amber). When this LED is lit, it indicates the power supply is near or exceeding its maximum output capability on at least one of its outputs.